Range : 0.5 A to 2500 A AC
Resolution : 0.1 A
Accuracy : 3 % ± 5 digits (5 Hz to 500 Hz)
Crest factor (50 Hz/60 Hz)
• 3.0 at 1100 A, 2.5 at 1400 A, 1.42 at 2500 A, add 2 % for C.F. > 2
LCD w/backlight : 3½ digits
Log rate/interval
• 1 sec minimum/adjustable by PC or front panel
Battery type : 2 AA, NEDA 15 A, IEC LR6
Battery life : 400 hours
Memory : Record up to 65,000 readings
RF communications : 2.4 GHZ ISM Band
RF communication range
• Open air, unobstructed: Up to 20 m
• Obstructed, sheetrock wall: Up to 6.5 m
• Obstructed, concrete wall or steel electrical enclosure: Up to 3.5 m
Operating temperature : -10 °C to +50 °C
Storage temperature : -40 °C to +60 °C
Temperature coefficient
• Add 0.1 X (specified accuracy)/ °C (<18 °C or >28 °C)
Operating humidity
• 90 % at 35 °C, 75 % at 40 °C, 45 % at 50 °C
Altitude
• Operating: 2,000 m
• Storage: 12,000 m
EMC : EN 61326-1:2013
Safety compliance
• IEC 61010-1, CAT IV 600 V, CAT III 1000 V, 3rd edition
Safety rating : CAT IV 600 V, CAT III 1000 V
Certifications : cCSAus, CE, FCC: T68-FBLE IC: 6627A-FBLE
Ingress Protection (IP) rating : IP42
Pollution degree : 2
Jaw opening : 25.4 cm (10 in) coil
Size (HxWxD) : 16.5x6.35x1.4 cm (6.5x2.5x1.4 in)
Weight: 0.22 kg (8 oz)